Failure Causes and Countermeasures
1. Valve fails to operate
| Presumed causes | Corrective action |
|---|---|
| Air pressure source (compressor) fault | Check compressor |
| Large leakage on Air piping | Check air piping |
| Presumed causes | Corrective action |
|---|---|
| Clogged or leaking on Air piping | Check air piping |
| Pressure Regulator Valve fault | Check and repair of Pressure Regulator |
| Presumed causes | Corrective action |
|---|---|
| Controller fault | Check controller |
| Clogged or leaking on signal Air piping | Check air piping |
| Presumed causes | Corrective action |
|---|---|
| Pilot Valve in Positioner fault | Check and repair Pilot Valve |
| Large leakage on Actuator | Check Actuator (Diaphragm) |
| Presumed causes | Corrective action |
|---|---|
| Valve Stem or Guide stick | Disassemble Body and check, repair or replace |
| Bend or breakage on Valve Stem | Repair or replace Valve Stem |
| Foreign matter entrapped on Seat or between Guide clearances | Disassemble and check valve port |
2. Vibration or Noise
| Presumed causes | Corrective action |
|---|---|
| Large clearance between Guide and Plug | Repair or replace Valve Plug and Guide |
| Loose connections (Valve Stem and Valve Plug, Valve Stem and Top Stem, Top Stem and Diaphragm) | Re-tighten connection |
| Poor de-aeration of fluid | De-aerate fluid |
| Flashing at outlet of the Valve Plug | Change valve type |
| Presumed causes | Corrective action |
|---|---|
| Natural vibration (double sealed valves except for cage type generate when unbalanced force of Valve Plug reverses) | Change valve type. (ex. cage type) |
| Presumed causes | Corrective action |
|---|---|
| Fluid flow to close Valve Plug (flow close) | Change valve Cv or Plug and control position |
| Presumed causes | Corrective action |
|---|---|
| Valve size too small (steam) | Enlarge valve size |
3. Valve fails to operate
| Presumed causes | Corrective action |
|---|---|
| Insufficient Air source capacity | Add compressor |
| Pressure Regulator fault | Repair or replace pressure Regulator Valve |
| Presumed causes | Corrective action |
|---|---|
| Inappropriate resistance or volume of Controller | Install valve or volume tank in signal circuit |
| Controller fault | Check controller |
| Presumed causes | Corrective action |
|---|---|
| Positioner fault | Check Pilot Valve Tighten Positioner connections |
| Large friction on Valve Stem | Check and repair Valve Stem and Guide |
| Large friction on Gland Packing | Replace Packing |
| Resonance with fluids turbulent wave motion (fluctuations in stem's thrust due to changes in fluid pressure) | Reduce differential pressure; Change Actuator, higher rigidity; Install rectify straight pipe on upstream |
4. Too Slow Action
| Presumed causes | Corrective action |
|---|---|
| Clogged guide with slurry or solids | Disassemble and clean Change valve type (Angle type) |
| Deteriorated and hardened gland Packing | Change packing and grease Change packing material |
| Presumed causes | Corrective action |
|---|---|
| Thrust by large differential pressure to Plug | Install Positioner Install big Actuator |
| Actuator Air volume is big | Install Positioner or booster |
| Air leakage from Actuator | Check Actuator |
5. Large hysteresis error
| Presumed causes | Corrective action |
|---|---|
| Valve Stem and Guide, no alignment | Check Valve Stem alignment |
| Deteriorated and hardened gland Packing | Change Packing |
| Foreign matter entrapped in Valve Plug | Disassemble and clean up |
| Clogged Valve Stem or Guide with slurry or solid | Disassemble and clean up |
6. Valve no move beyond certain travel
| Presumed causes | Corrective action |
|---|---|
| Manual Handle position is not set at “NEUTRAL” | Set Handle position “NEUTRAL” |
| Lack of supply air pressure | Check supply air pressure |
7. Large Leakage
| Presumed causes | Corrective action |
|---|---|
| Corrosion, erosion or damage on Valve Seat | Check Seat and repair or lap |
| Cavity in Valve Body | Repair or replace Body |
| Corrosion or erosion of thread in Valve Seat | Change Seat-Ring or Body |
| Presumed causes | Corrective action |
|---|---|
| Large differential pressure | Large differential pressure |
| Foreign matter entrapped in Valve Plug | Disassemble and clean up |
| Guide or port seizure | Repair or replace damaged parts |
| Presumed causes | Corrective action |
|---|---|
| Corrosion or erosion of Valve Plug or Cage | Change Valve Plug or Cage |
8. Leakage from Gland Packing
| Presumed causes | Corrective action |
|---|---|
| Loose Gland Nut | Re-tighten uniformly |
| Deteriorated and hardened Gland Packing | Change Packing. Change Packing material |
| Incorrect insert of Gland Packing | Re-insert correctly |
| No Grease | Add Grease |
| Corrosion, erosion, or damage of Valve Stem | Repair or change Valve Stem |