Failure Causes and Countermeasures

1. Valve fails to operate

Presumed causes Corrective action
Air pressure source (compressor) fault Check compressor
Large leakage on Air piping Check air piping
Presumed causes Corrective action
Clogged or leaking on Air piping Check air piping
Pressure Regulator Valve fault Check and repair of Pressure Regulator
Presumed causes Corrective action
Controller fault Check controller
Clogged or leaking on signal Air piping Check air piping
Presumed causes Corrective action
Pilot Valve in Positioner fault Check and repair Pilot Valve
Large leakage on Actuator Check Actuator (Diaphragm)
Presumed causes Corrective action
Valve Stem or Guide stick Disassemble Body and check, repair or replace
Bend or breakage on Valve Stem Repair or replace Valve Stem
Foreign matter entrapped on Seat or between Guide clearances Disassemble and check valve port

2. Vibration or Noise

Presumed causes Corrective action
Large clearance between Guide and Plug Repair or replace Valve Plug and Guide
Loose connections (Valve Stem and Valve Plug, Valve Stem and Top Stem, Top Stem and Diaphragm) Re-tighten connection
Poor de-aeration of fluid De-aerate fluid
Flashing at outlet of the Valve Plug Change valve type
Presumed causes Corrective action
Natural vibration (double sealed valves except for cage type generate when unbalanced force of Valve Plug reverses) Change valve type. (ex. cage type)
Presumed causes Corrective action
Fluid flow to close Valve Plug (flow close) Change valve Cv or Plug and control position
Presumed causes Corrective action
Valve size too small (steam) Enlarge valve size

3. Valve fails to operate

Presumed causes Corrective action
Insufficient Air source capacity Add compressor
Pressure Regulator fault Repair or replace pressure Regulator Valve
Presumed causes Corrective action
Inappropriate resistance or volume of Controller Install valve or volume tank in signal circuit
Controller fault Check controller
Presumed causes Corrective action
Positioner fault Check Pilot Valve
Tighten Positioner connections
Large friction on Valve Stem Check and repair Valve Stem and Guide
Large friction on Gland Packing Replace Packing
Resonance with fluids turbulent wave motion (fluctuations in stem's thrust due to changes in fluid pressure) Reduce differential pressure;
Change Actuator, higher rigidity;
Install rectify straight pipe on upstream

4. Too Slow Action

Presumed causes Corrective action
Clogged guide with slurry or solids Disassemble and clean
Change valve type (Angle type)
Deteriorated and hardened gland Packing Change packing and grease
Change packing material
Presumed causes Corrective action
Thrust by large differential pressure to Plug Install Positioner
Install big Actuator
Actuator Air volume is big Install Positioner or booster
Air leakage from Actuator Check Actuator

5. Large hysteresis error

Presumed causes Corrective action
Valve Stem and Guide, no alignment Check Valve Stem alignment
Deteriorated and hardened gland Packing Change Packing
Foreign matter entrapped in Valve Plug Disassemble and clean up
Clogged Valve Stem or Guide with slurry or solid Disassemble and clean up

6. Valve no move beyond certain travel

Presumed causes Corrective action
Manual Handle position is not set at “NEUTRAL” Set Handle position “NEUTRAL”
Lack of supply air pressure Check supply air pressure

7. Large Leakage

Presumed causes Corrective action
Corrosion, erosion or damage on Valve Seat Check Seat and repair or lap
Cavity in Valve Body Repair or replace Body
Corrosion or erosion of thread in Valve Seat Change Seat-Ring or Body
Presumed causes Corrective action
Large differential pressure Large differential pressure
Foreign matter entrapped in Valve Plug Disassemble and clean up
Guide or port seizure Repair or replace damaged parts
Presumed causes Corrective action
Corrosion or erosion of Valve Plug or Cage Change Valve Plug or Cage

8. Leakage from Gland Packing

Presumed causes Corrective action
Loose Gland Nut Re-tighten uniformly
Deteriorated and hardened Gland Packing Change Packing. Change Packing material
Incorrect insert of Gland Packing Re-insert correctly
No Grease Add Grease
Corrosion, erosion, or damage of Valve Stem Repair or change Valve Stem